Technical Data:
Parameters(25℃)/Model | SCY6- | |||
100A | 200A | 300A | 500A | |
Nominal Rms Current (Ipn) | ±100AT | ±200AT | ±300AT | ±500AT |
Measuring Range (Ip) | 300AT | 600AT | 750AT | 1000AT |
Load resistance Rmax | ≥10KΩ | |||
Output Voltage | ±4V or 5V | |||
Working voltage | DC ±12V or ±15V (±5%) | |||
Accuracy @ Ta=25°C | ±1% | |||
Linearity @ Ta=25°C | ±1% | |||
Withstand voltage | 2.5 kVrms/50Hz/1min | |||
Offset Voltage | <±30mV | <±15mV | ||
Offset temperature characteristics | < ±0.08%/°C | < ±0.05%/°C | ||
Thermal drift of Vo | <±2mV/°C | <±1mV/°C | ||
Hysteresis offset | <30mV | <20mV (If=F.S. 0<--->Nominal input current) | ||
Response time | < 5uS | |||
Current consumption | <±15mA | |||
Operating temperature | -20~+80 °C | |||
Storage temperature | -40~+85 °C | |||
Hole inside diameter (mm) | ø21 |
Dimension(mm):
Notes:
1. Size error: ±1mm;
2. Primary aperture: φ21mm;
3. Y6T output terminal: 2EDGVC-5.08-4P
4. Y6R output interface: Amphenol BD-04AFMM-QL8XX
5. The IP indication direction is the positive direction of the current, OFS is the zero adjustment, and GIN is the output regulation;
6. Incorrect wiring may cause damage to the sensor.
Instructions:
1. SCY6 Series 's up and down can open and close without removing the busbarline, easy to install.
2. Based on open-loop principle, it can measure DC, AC and Pulse current.
3. Square perforation, mainly measure wire conductor current.
4. Features: High accuracy, low power consumption, high liability and strongoverload capacity.
Caution: Incorrect wiring may damage the sensor.
Weight & Package:
96pcs per box